Chào mừng đến với Antek Việt Nam - Nhà cung cấp thiết bị công nghiệp FDI!
Model: Yaskawa CIPR-UT4P0216FSA
- Input power supply voltage: 400 V 3-phase
- Customized Specifications: 24 V Power Supply Unit Built-in
- Protection Design: NEMA Type 1
- Environmental specification: Vibration resistant
- Rated input capacity [kVA]*2 (ND rating): 180
- Series: UT Series
- Region code: Asia (Singapore and Taiwan)
- T: Asia (Singapore and Taiwan)
- A: Japan
- B: China
- C: Europe
- D: India
- K: Korea
- U: the Americas
- Input power supply voltage: 400 V 3-phase
- Rated Output Current: Check specification & datasheet
- Customized Specifications: 24 V Power Supply Unit Built-in
- Protection Design: NEMA Type 1
- Environmental specification: Vibration resistant
- Input current [A]*1 (ND Rating): 197
- Rated input capacity [kVA]*2 (ND rating): 180
- Rated output current (100 % ED) [A]*3,4216
- Overload tolerance*6: HD rating: 150 % of rated output current for 60 s ND rating: 120 % of rated output current for 60 s (Derating may be required for applications that start and stop frequently)
- Carrier frequency: 4 kHz (User adjustable up to 6 kHz. Derating may be required.)
- Max. output voltage [V]: Proportional to input voltage *5 *7
- Max. output frequency [Hz]: 400 Hz (User-adjustable)
- Rated voltage / Rated frequency: Three-phase (CIMR-Uo4oooo) 380 to 480 VAC 50/60 Hz
- Allowable voltage fluctuation: -15 to +10 %
- Allowable frequency fluctuation: ±3 % (Frequency fluctuation rate: 1 Hz/100 ms or less)
- Allowable phase power supply voltage unbalance: 2 % or less
- Harmonic current harmonic distortion*5: 5 % or less (IEEE519 compliant)
- Input power factor: 0.98 % or more (During rated operation)