Chào mừng đến với Antek Việt Nam - Nhà cung cấp thiết bị công nghiệp FDI!

0
Sản phẩm yêu thích
Giỏ hàng
Tổng tiền : 0
 

Biến tần Yaskawa CIMR-RT2A0035AKA

Model: Yaskawa CIMR-RT2A0035AKA

  • Liên hệ
  • Input power supply voltage: 200 V 3-phase
  • Customized Specifications: Standard mode
  • Protection Design: IP00
  • Environmental specification: Gas resistant

Download datasheet

Thông tin chung Biến tần Yaskawa CIMR-RT2A0035AKA

- Series: CIMR-RT1000 Series

- Region code: Asia (Singapore and Taiwan)

- T: Asia (Singapore and Taiwan)

- A: Japan

- B: China

- C: Europe

- D: India

- K: Korea

- U: the Americas

- Input power supply voltage: 200 V 3-phase

- Rated Output Current: Check specification & datasheet

- Customized Specifications: Standard mode

- Protection Design: IP00

- Environmental specification: Gas resistant

Thông sỗ kỹ thuật Biến tần Yaskawa CIMR-RT2A0035AKA

- Regeneration Capacity kW: 35

- Rated Output Current (DC) A: 138

- Rated Input Current (AC) A: 102

- Rated Voltage/Rated Frequency: 200 to 240Vac 50/60Hz

- Allowable Voltage Fluctuation: - 15 to + 10%

- Allowable Frequency Fluctuation: ± 2%

- Control Method: 120°excitation method

- Input Power Factor: 0.9 min. (for rated load)

- Overload Protection: 30 s at approx. 150% of rated current.

- Regenerative Torque: 150% 30 s, 100% 25% ED 60 s, 80% continuous

- Main Control Functions: Cooling Fan on/off Switch, Removable Terminal Block with Parameter Backup, MEMOBUS/Modbus Comm. (RS-422/RS-485 max, 115.2 kbps)

- Momentary Overcurrent Protection: Operation stops for approx. 250% or higher of the rated power supply current.

- Fuse burnout: Operation stops if the fuse burns out.

- Overloads: Operation stops for 150% of the rated power supply current for 30 s.

- Overvoltage Protection Output: Stops when DC bus voltage exceeds approx. 410 Vdc

- Overvoltage Protection Input: Stops when input voltage exceeds approx. 227 Vac

- Undervoltage Protection Output: Stops when DC bus voltage falls below approx. 190 Vdc

- Undervoltage Protection Input: Stops when input voltage falls below approx. 150 Vac

- Momentary Power Loss: Immediately stops after Momentary Power Loss is detected.

- Power Supply Frequency Fault: Operation stops for a deviation of ± 6 Hz or more from the rated input frequency.

- Heatsink Overheat Protection: Protection by thermistor

- Charge LED: Charge LED remains lit until DC bus has fallen below approx. 50 V

- Area of Use: Indoors (Protected from corrosive gases and dust)

- Ambient Temperature: − 10 to +40°C (UL Type1), − 10 to +50° C (IP00, IP20)

- Humidity: 95% RH or less (no condensation)

- Shock: (2A03P5 to 2A0053, 4A03P5 to 4A0073)10 to 20 Hz:9.8 m/s2,20 to 55 Hz:5.9 m/s2 (2A0073 to 2A0105, 4A0105 to 4A0300)10 to 20 Hz:9.8 m/s2,20 to 55 Hz:2.0 m/s2

- Storage Temperature: − 20 to +60°C(short-term temperature during transportation)

- Altitude: Up to 1000 meters (derating required at altitudes from 1000 to 3000 m) . Open Type enclosure(IP00) Enclosed Wall-Mounted (IP20/UL Type1)*2. UL508C, IEC/EN61800-5-1, IEC/EN61800-3